Enter at least 2 characters

Starter PRK 64-40 In=40A Ir=25-40A Ue 660V IEK

Description

PRK motor-starters of IEK trade mark are designed for managing and protecting three-phase asynchronous electric motors from overloads, short-circuit and open-phase operating conditions. They combine the functions of a modular circuit breaker serving for motor protection and a manual starter. These starters are used at industrial sites, agriculture and construction. It is possible to apply them for the local management of separate electric motors as well as residential and administrative building automation.

  • Life time:

    10 years

  • Warranty:

    3 years

Advantages

  • High accuracy of operation.
  • Convenient adjustment.
  • Wide range.
Starter PRK 64-40 In=40A Ir=25-40A Ue 660V IEK

Design Features

PRK64 series manual starter interlocking is provided with a padlock.

PRK64 series manual starter interlocking is provided with a padlock.

Specifications

Nominal rated current, A40.0
Setting range over-current release, A25...40
Number of poles3
Switch off techniqueThermomagnetic
Rated insulation voltage Ui, B660
Weight, kg0,79
Width, mm63.5
Height, mm112.5
Depth, mm78.0
Adjustment range undelayed short-circuit release, A-
Phase failure sensitiveYes
Rated permanent current Iu, A40
Device constructionBuilt-in device fixed built-in technique
With integrated auxiliary switchNo
With integrated under voltage releaseNo
Rated short-circuit breaking capacity lcu at 400 V, AC, kA15
Nominal the working disconnected current to Ics of 400 V, kA15.0
Nominal the working disconnected current to Ics of 660 V, kA3.00
The rated limit disconnected current to Icu of 230 V, kA50
The rated limit disconnected current to Icu of 400 V, kA15
The rated limit disconnected current to Icu of 660 V, kA3
Heat loss, W per pole3.0
Nominal fuse current Icc-Icu 400V aM, A250
Nominal fuse current Icc-Icu 400V GL-gG, A315
With thermal protectionYes
Rated operating voltage, B660
Nominal frequency, Hz50
Release class - protection10А
Nominal power of ED control in application of AC-3 230V, kW11.00
Nomininal power of ED control in application of AC-3 400V, kW19.00
Nominal power of ED control in application of AC-3 660V, kW30.00
Solenoid release setpoint, A480.0
Type of electric connectionScrew connection
Mounting methodDIN rail
Degree of protection (IP)IP20
Connection type main current circuitScrew connection
Ambient classUHL3.1
Environmental applicationsВ
Electrical or Mechanical Wear Resistance, cycles B on O10000
Ambient temperature, °C-25...40

Logistics parameters

IndividualTransport
Quantity124
Unitspc; 1pc; 1
Type of packagingBOX/BOXBOX/BOX
Packaging materialCARDBOARDFIVE-LAYER CORPORATED
Barcode46060564816794606056468267
Gross weight, kg0.79219
Netto weight, kg0.74117.879
Volume, m^30.0011440.027456
Length, cm11.944
Height, cm10.424
Width, cm6.426
Method of applying informationMoldMold