Enter at least 2 characters

Circuit breaker BA47-100MA without thermal release 3P 16A 10kA D IEK

Description

Automatic switches VA47-100MA are designed to protect distribution and group circuits, emergency security systems, fire extinguishing and ventilation systems. Recommended for use in input distribution devices of household and industrial electrical installations.

  • Life time:

    15 years

  • Warranty:

    10 years

Advantages

  • Reliable short circuit protection.
  • Complete set of supplementary devices with the possibility of simple independent installation:
  • – State contact KS47;
  • – State contact KSV47;
  • – Undervoltage trip RMM47;
  • – Low-voltage release RN47.
  • Indication of contact position.
  • Latching on DIN-rail with double locking.
  • Wide operating temperature range from –40 to +50° С.
  • Updated wider engagement lever with improved contact area.
  • Notches on contact terminals reduce heat loss and increase mechanical stability of the connection.
  • Higher switching capacity of 10000A provides for installing VA47-100MA as input circuit breakers.
Circuit breaker BA47-100MA without thermal release 3P 16A 10kA D IEK

Specifications

Primary current, A16
Frequency, Hz50
Nominal rated current, A16.0
Number of poles3
Release characteristicD
Rated switching capacity, kA10.0
Voltage typeAC
Nominal rated voltage, B400
Power loss, W10.5
Rated short-circuit breaking capacity EN 60898, kA10
Width in number of modular spacings4,5
Max. cross section incoming cable, mm²35
Frequency, Hz50
Degree of protection (IP)IP20
Mounting methodDIN-rail (DRA)
Mechanical wear resistance, cycles20000
Electric wear resistance, cycles8000
Possibility of busbars connectionPIN (pin), FORK (plug)
Weight of one pole, kg0,22
Number of poles (total)3
Additional equipment possibleYes
Type of electric connectionScrew connection
Voltage type for actuatingAC
Thermal releaseNo
Electromagnetic releaseYes
Mounting rail typeTN-35
Operation modeContinuous-S1
Number of protected poles3
Connectable conductor cross section solid-core, mm²2,5...35
Connectable conductor cross section multi-wired, mm²2,5...35
Ambient temperature during operating, °C40
Rated short-circuit breaking capacity Icn EN 60898 at 400 V, kA10.0
Rated short-circuit breaking capacity Icn EN 60898 at 230 V, kA10.0

Logistics parameters

IndividualGroupTransport
Quantity1440
Unitspc; 1pc; 1pc; 1
Type of packagingBOX/BOXBOX/BOXBOX/BOX
Packaging materialCARDBOARDTHREE-LAYER CORRUGATEDFIVE-LAYER CORPORATED
Barcode461008400709146100840071074610084007114
Gross weight, kg0.6062.42424.24
Netto weight, kg0.62.424
Volume, m^30.0008430.0026830.03372
Length, cm9.234.551.2
Height, cm7.78.118.3
Width, cm8.39.636
Method of applying informationStickerStickerSticker

Compatible Products