Starter PRK 32-6,3 In=6,3A Ir=4-6,3A Ue 660V IEK
Product ID:
Main specifications
Nominal rated current, A | 6.3 |
Setting range over-current release, A | 4...6,3 |
Number of poles | 3 |
Switch off technique | Thermomagnetic |
The rated limit disconnected current to Icu of 660 V, kA | 3 |
Description
PRK motor-starters of IEK trade mark are designed for managing and protecting three-phase asynchronous electric motors from overloads, short-circuit and open-phase operating conditions. They combine the functions of a modular circuit breaker serving for motor protection and a manual starter. These starters are used at industrial sites, agriculture and construction. It is possible to apply them for the local management of separate electric motors as well as residential and administrative building automation.
Life time:
10 years
Warranty:
3 years
Advantages
- High accuracy of operation.
- Convenient adjustment.
- Wide range.
Design Features
Specifications
Nominal rated current, A | 6.3 |
Setting range over-current release, A | 4...6,3 |
Number of poles | 3 |
Switch off technique | Thermomagnetic |
The rated limit disconnected current to Icu of 660 V, kA | 3 |
Switching overvoltage, B | ≤ 8000 |
Rated surge voltage invariability, kV | 8 |
With thermal protection | Yes |
Rated operating voltage, B | 230/400/600 |
Nominal frequency, Hz | 50 |
Release class - protection | 10 |
Nominal power of ED control in application of AC-3 230V, kW | 1.10 |
Nomininal power of ED control in application of AC-3 400V, kW | 2.20 |
Nominal power of ED control in application of AC-3 660V, kW | 4.00 |
Solenoid release setpoint, A | 78.0 |
Type of electric connection | Screw connection |
Mounting method | DIN rail |
Degree of protection (IP) | IP20 |
Connection type main current circuit | Screw connection |
Ambient class | UHL3.1 |
Environmental applications | В |
Electrical or Mechanical Wear Resistance, cycles B on O | 10000 |
Ambient temperature, °C | -25...40 |
Rated insulation voltage Ui, B | 660 |
Maintainability | None |
Weight, kg | ≤ 0,26 |
Width, mm | 44.5 |
Height, mm | 90.0 |
Depth, mm | 81.0 |
Adjustment range undelayed short-circuit release, A | - |
Phase failure sensitive | Yes |
Rated permanent current Iu, A | 6 |
Device construction | Built-in device fixed built-in technique |
With integrated auxiliary switch | No |
With integrated under voltage release | No |
Rated short-circuit breaking capacity lcu at 400 V, AC, kA | 100 |
Nominal the working disconnected current to Ics of 400 V, kA | 100.0 |
Nominal the working disconnected current to Ics of 660 V, kA | 2.25 |
The rated limit disconnected current to Icu of 230 V, kA | 100 |
The rated limit disconnected current to Icu of 400 V, kA | 100 |
Logistics parameters
Individual | Transport | |
---|---|---|
Quantity | 1 | 50 |
Units | pc; 1 | pc; 1 |
Type of packaging | BOX/BOX | BOX/BOX |
Packaging material | CARDBOARD | FIVE-LAYER CORPORATED |
Barcode | 4606056113259 | 4606056113266 |
Gross weight, kg | 0.316 | 15.8 |
Netto weight, kg | 0.3 | 15.01 |
Volume, m^3 | 0.000501 | 0.02505 |
Length, cm | 9.6 | 48.8 |
Height, cm | 8.9 | 27 |
Width, cm | 5.2 | 19 |
Method of applying information | Mold | Mold |